Low Voltage Armoured Power Cable

Low Voltage Armoured Power Cable

HOLDONE, a renowned manufacturer, specialises in producing high quality Low Voltage Steel Ribbon Power Cables that provide a solid guarantee of energy transmission in a wide range of industries. These cables are an integral part of modern power systems and are used in a wide range of applications such as construction, industry, energy distribution, and outdoor applications. The core features of our Low Voltage Steel Ribbon Power Cables are their superior design and high quality materials. The copper or aluminium conductors inside the cable ensure efficient and stable current transmission. And the special cross-linked polyethylene (XLPE) or polyvinyl chloride (PVC) insulation not only prevents current leakage, but also effectively resists the effects of humidity and other environmental factors.

Low Voltage Armoured Power Cable Parameter

Nominal Conductor Area

No. and Diameter of  Wires

Nominal Diameter of Conductor

Maximum Conductor
Resistance at 20ºC

Nominal Weight per km of

(mm2)

(no./mm)

(mm)

(0/km)

Conductor (kg/km)

1

7 / 0.43

1.29

18.1

9.2

1.5

7 / 0.53

1.59

12.1

14

2.5

7 / 0.67

2.01

7.41

22.4

4

7 / 0.85

2.55

4.61

36.1

6

7 / 1.04

3.12

3.08

54

10

7 / 1.35

4.05

1.83

90.8

16

7 / 1.70

4.69

1.15

145

25

7 / 2.14

5.9

0.727

229

35

7 / 2.52

6.95

0.524

317

50

19 / 1.78

8.4

0.387

429

70

19 / 2.14

10.1

0.268

620

95

19 / 2.52

11.9

0.193

860

120

37 / 2.03

13.5

0.153

1086

150

37 / 2.25

14.9

0.124

1334

185

37 / 2.52

16.9

0.0991

1673

240

61 / 2.25

19.2

0.0754

2199

300

61 / 2.52

21.5

0.0601

2759

400

61 / 2.85

24.3

0.047

3528

500

61 / 3.20

27.3

0.0366

4448

630

127 / 2.52

32.76

0.0283

5744

800

127 / 2.85

37.05

0.0221

7346

1000

127 / 3.20

41.6

0.0176

9260

No. Cores

Conduct or Cross
Section Area (mm²)

Cable Cross Section Area  (mm²)

Actual Armour Cross Section Area (mm²)

Overall Diameter (mm)

Gland
Size

Cleat Size

2

1.5

114.93

15

12.1

20S

5

2

2.5

145.19

17

13.6

20S

6

2

4

169.63

19

14.7

20S

6

2

6

198.46

22

15.9

20

7

2

10

254.34

26

18

20

8

2

16

326.69

42

20.4

25

9

2

25

455.94

42

24.1

25

10

2

35

426.17

60

23.3

25

10

2

50

522.53

68

25.8

32

11

2

70

660.19

80

29

32

12

2

95

860.05

113

33.1

40

14

2

120

1023.02

125

36.1

40

16

2

150

1212.42

138

39.3

40

18

2

185

1568.5

191

44.7

50

20

2

240

1884.79

215

49

50

T9

2

300

2246.87

235

53.5

63

T9

2

400

2732.59

265

59

63

T10

No. Cores

Conduct or Cross Sec- tion Area (mm²)

Cable Cross Section Area  (mm²)

Actual Armour Cross Section Area (mm²)

Overall Diameter (mm)

3

1.5

124.63

16

12.6

3

2.5

156.07

19

14.1

3

4

183.76

20

15.3

3

6

216.31

23

16.6

3

10

298.5

39

19.5

3

16

366.25

45

21.6

3

25

510.45

62

25.5

3

35

615.44

68

28

3

50

637.62

78

28.5

3

70

813.92

90

32.2

3

95

1074.67

128

37

3

120

1281.25

141

40.4

3

150

1625.15

201

45.5

3

185

1946.83

220

49.8

3

240

2383.27

250

55.1

3

300

2844.87

269

60.2

3

400

3481.91

304

66.6

No. Cores

Conduct or Cross Section Area (mm²)

Cable Cross Section Area  (mm²)

Actual Armour Cross Section Area (mm²)

Overall Diameter (mm)

Gland
Size

Cleat Size

4

1.5

143.07

17

13.5

20s

6

4

2.5

176.63

20

15

20s

6

4

4

211.13

23

16.4

20

7

4

6

274.51

36

18.7

20

8

4

10

349.49

43

21.1

25

9

4

16

411.66

49

22.9

25

11

4

25

597.98

70

27.6

32

12

4

35

725.47

78

30.4

32

12

4

50

803.84

90

32

32

14

4

70

1115.71

131

37.7

40

16

4

95

1365.03

147

41.7

50

18

4

120

1741.45

206

47.1

50

20

4

150

2073.94

230

51.4

50

TC9

4

185

2514.79

255

56.6

63

TC10

4

240

3115.75

289

63

63

TC11

4

300

3715.75

319

68.8

75

TC12

4

400

4788.19

452

78.1

75

TC14

No. Cores

Conduct or Cross Section Area (mm²)

Stranding mm

Approx weight kg/km

Approx overall diameter

Gland size mm

Single cleat

Nom. Max. DC-resist conductor 20oC ohm/km

Current rating laid direct amp

5

1.5

7/0.53

395

13.72

20s

0.6

12.1

32

5

2.5

7/0.67

497

15.46

20s

0.6

7.41

42

5

4

7/0.85

674

17.38

20

0.7

4.61

55

5

6

7/1.04

868

19.05

20

0.8

3.08

69

5

10

7/1.35

1197

22.06

25

0.9

1.83

92

5

16

7/1.70

1780

24.14

25

1.1

1.15

119

5

25

7/2.14

2435

28.4

32

1.2

0.727

152

5

35

7/2.52

2800

33

40

1.4

0.524

182

5

50

19/1.78

3850

38

40

1.6

0.387

217

5

70

19/2.14

5100

42.9

50s

1.8

0.268

266

5

95

19/2.52

7700

52.1

50

TC9

0.193

319

Get a sample