Concentric Cable is a cable with a special construction consisting of one or more insulated conductors surrounding a centre conductor. The design is unique in that the centre conductor is coaxial with the insulated conductors, giving it excellent performance in transmitting signals and power. This design effectively reduces signal interference and energy loss, providing high-quality signal transmission for a variety of applications. holdone, the manufacturer of Concentric Cable, has won praise in the industry for the excellent quality of its products and its outstanding performance. Whether in the field of construction, energy, communication or transport, Concentric Cable plays an indispensable role in bringing convenience and safety to people’s life and work. holdone will continue to make unremitting efforts to promote the innovation and development of Concentric Cable technology, and provide customers around the world with even better cable solutions.

Concentric Cable parameters

Conductor

Stranding

Nominal O.D. (Mils)

Allowable Ampacities

Approximat e Net Weight Per 1000′ (Lbs)

Standard Package

Size/Const. AWG or kcmil

Phase Conductor & Neutral

Equipment Ground Conductor

 

60°C

75°C

90°C

Dwelling

 

 

8-8-8

7

586

40

50

55

231

B

6-6-6

7

669

55

65

75

338

B

4-4-4

7

764

70

85

95

100

498

B

3-3-3

7

829

85

100

110

110

611

B

2-2-2

7

896

95

115

130

125

752

B

1-1-1

19

1021

110

130

150

150

948

C

1/0-1/0-1/0

19

1114

125

150

170

175

1169

C

2/0-2/0-2/0

19

1209

145

175

195

200

1444

C

3/0-3/0-3/0

19

1317

165

200

225

225

1792

C

4/0-4/0-4/0

19

1438

195

230

260

250

2226

C

Conductor

Stranding

Nominal O.D. (Mils)

Allowable Ampacities

Approximat e Net Weight Per 1000′ (Lbs)

Standard Package

Size/Const. AWG or kcmil

Phase Conductor & Neutral

Equipment Ground Conductor

 

60°C

75°C

90°C

Dwelling

 

 

8-8-8-8

7

7

645

40

50

55

286

B

6-6-6-6

7

7

738

55

65

75

424

B

4-4-4-6

7

7

844

70

85

95

100

585

B

3-3-3-5

7

7

910

85

100

110

110

719

B

2-2-2-4

7

7

984

95

115

130

125

887

B

1-1-1-3

19

7

1132

110

130

150

150

1117

C

1/0-1/0-1/0-2

19

19

1235

125

150

170

175

1382

C

2/0-2/0-2/0-1

19

19

1342

145

175

195

200

1713

C

3/0-3/0-3/0-1/0

19

19

1462

165

200

225

225

2129

C

4/0-4/0-4/0-2/0

19

19

1598

195

230

260

250

2650

C

Conductor

Stranding

Nominal O.D. (Mils)

Allowable Ampacities

Approximat e Net Weight Per 1000′ (Lbs)

Standard Package

Size/Const. AWG or kcmil

Phase Conductor & Neutral

Equipment Ground Conductor

 

60°C

75°C

90°C

Dwelling

 

 

10-10-10

1

12

428 X 283

30

30

30

127

ABC

8-8-8

7

8

587 X 380

40

50

60

211

ABC

6-6-6

7

12

659 X 416

55

65

75

308

BCE

4-4-4

7

12

815 X 506

70

85

95

100

471

BCE

3-3-3

7

12

883 X 548

85

100

110

110

583

B

2-2-2

7

15

994 X 578

95

115

130

125

718

BD

1-1-1

19

14

1093 X 664

110

130

150

150

904

B

1/0-1/0-1/0

19

19

1179 X 707

125

150

170

175

1123

BC

2/0-2/0-2/0

19

18

1283 X 767

145

175

195

200

1379

BC

3/0-3/0-3/0

19

14

1429 X 862

165

200

225

225

1712

BC

4/0-4/0-4/0

19

18

1541 X 918

195

230

260

250

2146

BC

Conductor

Stranding

Nominal O.D. (Mils)

Allowable Ampacities

Approximat e Net Weight Per 1000′ (Lbs)

Standard Package

Size/Const. AWG or kcmil

Phase Conductor & Neutral

Equipment Ground Conductor

 

60°C

75°C

90°C

Dwelling

 

 

6-6-8

7

8

659 X 416

55

65

75

281

BC

4-4-6

7

12

790 X 481

70

85

95

100

420

BC

3-3-5

7

12

843 X 508

85

100

110

110

515

BC

2-2-4

7

12

929 X 563

95

115

130

125

639

BC

Get a sample